Float or Thermodynamic? Choosing the Steam Trap Type
A float trap discharges continuously and reacts fast to load swings; a thermodynamic trap cycles but is simple and robust. The choice follows the character of the load.
Once it is settled that a steam circuit needs a trap, the next question is which type. Float and thermodynamic traps do the same job — pass condensate, hold back steam — but by two completely different mechanisms. That difference is what makes each one right for different lines. The decision follows the character of the load.
Two mechanisms, two behaviours
A float trap contains a ball floating inside the body. As condensate collects the float rises, the valve linked to it opens, and condensate flows. When the load increases the float rises further and the valve opens wider. The result is continuous, proportional discharge: whatever arrives is passed, and condensate does not sit waiting inside the body.
In a thermodynamic trap the only moving part is a thin disc. It seats and lifts according to the pressures above and below it and the temperature difference between steam and condensate. Operation is continuous but flow is not: the disc opens, releases some condensate, closes, re-establishes a pressure balance, and opens again. A thermodynamic trap cycles.
Which load wants which type
| Line character | Suitable type | Why |
|---|---|---|
| Variable, heavy condensate load (heat exchanger, coil, process vessel) | Float | Discharge opens with load; condensate does not blanket the heat transfer surface |
| Main steam distribution header drainage | Thermodynamic | Load is light and steady; compact body, simple construction |
| Tracing branches | Thermodynamic | Many points, small loads, outdoor exposure |
| Start-up points with sudden load surges | Float | Fast response to a step increase; nothing accumulates |
The price of cycling
Cycling is not a problem as long as it matches the load. But if very little condensate reaches the trap, the disc keeps cycling anyway, and each cycle passes a little steam into the chamber behind it. Those idle cycles mean both steam loss and needless wear on the disc and seat. So a thermodynamic trap intended for a very lightly loaded point has to be selected against an estimate of that load — “small line, small trap” misleads here.
The float type's corresponding weakness is the condensate that stays inside it. Continuous discharge requires the float to float, which means some water always remains in the body.
Note: Where freezing is possible, that difference decides the matter. When the line stops, water left in a float body can freeze and crack it; a thermodynamic trap tends to drain itself and tolerates freezing better. If a float trap is to be used outdoors, drainage and insulation belong in the design.
Body material follows the environment
A practical consequence ties the two types together. Because their failure modes differ, so does the way you detect them: a float trap most often fails by refusing to open and backing condensate up into the line, whereas a thermodynamic trap more often fails by staying open and passing live steam. The first shows itself as poor heat transfer, the second as a bill. Knowing which type sits where tells the maintenance team which of those two symptoms to look for.
Thermodynamic traps come in two body families. Forged steel is the standard choice on indoor distribution headers: mechanically robust and economical. Stainless bodies are preferred in corrosive atmospheres, outdoors, and in processes washed down as part of cleaning. What decides this is not the steam inside but the environment outside the trap: sea air, chemical vapours or a pressure-washer aimed at the surface all attack the body from without.
In short: variable load with a heat transfer surface points to a float trap; light, steady load spread over many points points to a thermodynamic one. Chosen correctly, a trap will not remind you of itself for years.
From the catalog
Products mentioned in this article
The technical values of the products below are extracted from the company's printed catalog, not from the article text.
Ball Float Steam Trap Type:20
Steam Traps
- Connection
- DIN2533 BSP & NPT
- Working pressure
- PN14
- Working temperature
- -10°C / +250°C
Ball Float Steam Trap Type:25
Steam Traps
- Connection
- DIN2533 BSP & NPT
- Working pressure
- PN14
- Working temperature
- -10°C / +250°C
Forged Steel Body Thermodynamic Steam Trap
Steam Traps
- Connection
- EN1092-1 BSP & NPT
- Working pressure
- PN46
- Working temperature
- -10°C / +400°C
Stainless Steel Body Thermodynamic Steam Trap
Steam Traps
- Connection
- EN1092-1 BSP & NPT
- Working pressure
- PN40
- Working temperature
- -10°C / +400°C
Read next
Related articles
Pneumatic or Electric Actuator? Decision Criteria and Torque Margin
The first thing deciding actuator type is whether the plant has compressed air. Then come speed, fail position, environment and co...
Static Balancing Valves: Measuring Flow and Locking the Setting
In an unbalanced system the branch near the pump takes too much flow and the far branch too little. A static balancing valve makes...
Sight Flow Indicators: They Measure Nothing, Yet Tell You Plenty
A sight flow indicator gives no flow rate; it is not an instrument. It is, however, the fastest way to confirm by eye that a pump...
Let us select the right product for your project
You can write to our technical team with questions about the topic in this article.